# Warnings

## batterX h-Series

```
ID          Description

1           [F101] Connection or network error
16640       [W101] Grid failure / No AC supply at inverter input
16641       [W07] Island operation, grid outside tolerances
16642       [W09] Incorrect phase order (L1/L2/L3) or phase loss at the mains input
16643       [W08] Incorrect mains/grid signal, outside of tolerance
16657       [W51] Voltage loss at AC input, or outside of tolerance
16658       [W01] Gird failure – voltage too high
16659       [W02] Grid failure – voltage too low
16660       [W05] Average grid voltage exceeded limit
16738       [W52] Grid frequency at AC input outside of tolerance
16739       [W03] Grid frequency outside of tolerance, too high
16740       [W04] Grid frequency outside of tolerance, too low
16864       Grid charging power reduced (§ 14a)
17152       [F03] DC bus start time exceeded
17169       [F01] Internal overvoltage of the DC bus
17170       [F02] Internal undervoltage of the DC bus
17408       [W15] Battery disconnected
17425       [F22] Battery voltage too high
17426       [W13] Battery low
17427       [W14] Deactivation of battery discharge for emergency power operation
17443       [W16] Deactivation of battery discharge for normal operation
17457       [F32] Inverter DC-DC current too high
17569       [W104] Calibration charge
17570       [W103] Calibration charge not completed
17585       [b0] Battery discharge stopped by BMS
17586       [b1] Battery charging stopped by BMS
17587       [b2] Start of battery charging from the BMS
17649       [F102] BMS communication error
17665       [F26] AC output short circuit
17682       [F34] AC output loss - voltage too high
17683       [F33] AC output loss – voltage too low
17761       [F23] AC output overload
17762       [F103] AC output overload phase L1
17763       [F104] AC output overload phase L2
17764       [F105] AC output overload phase L3
17766       [W105] AC output load limit phase L1
17767       [W106] AC output load limit phase L2
17768       [W107] AC output load limit phase L3
17921       [W53] PV input 1 disconnected
17922       [W54] PV input 2 disconnected
17929       [F38] Short circuit at PV input
17937       [F09] PV voltage too high
17953       [F106] PV input 1 voltage too high
17954       [F107] PV input 2 voltage too high
17969       [F11] PV current too high
18065       [F13] PV insulation fault
18176       [F04] Inverter start time exceeded
18177       [F07] Inverter relay error
18225       [F05] Inverter current too high
18227       [F14] Inverter current (DC) too high 
18688       [W12] Internal temperature limit reached
18689       [F06] Overtemperature
18690       [F35] Internal communication problem with the control board
18693       [F27] Fan stop
18694       [W10] Emergency stop contact (EPO) open
18704       [F12] Earth fault on the PV side
18705       [F16] Fault in the PV earth fault sensor
18707       [F18] Connection failure between MCU and DSP
18708       [F17] Communication error between MCU and DSP
18709       [F08] Current sensor error 
18721       [F60] External power source at the inverter output
18722       [F61] Driver failure on the relay card
18723       [F62] Loss of communication with the relay card
18725       [F90] Inverter serial number missing
18912       [W110] Emergency bypass activated
18913       [F108] Protected output switched off
18928       [F109] Grid energy meter not working
18931       [F110] Energy meter of the external PV system is not functioning
18933       [F111] Energy meter external energy storage not working
18938       [F112] User energy meter 1 is not functioning
18939       [F113] User energy meter 2 is not functioning
18940       [F114] User energy meter 3 is not functioning
18941       [F115] User energy meter 4 is not functioning
```

## batterX i-Series

```
ID          Description

12544       [E002] Mains Lost
12545       [E003] Grid Voltage Fault
12546       [E004] Grid Frequency Fault
12547       [E005] DCI Fault
12548       [E006] ISO Over Limitation
12549       [E007] GFCI Fault
12550       [E008] PV Over Voltage
12551       [E001] DC BUS Over Votlage
12552       [E009] Over Temperature
12553       [E010] N-PE Check Fault
12554       [E030] DC arc Fault
12555       [E033] DC BUS Voltage Imbalance
12609       [E020] SPI Fault
12610       [E021] E2 Fault
12611       [E022] GFCI Sensor Fault
12612       [E023] AC Current Sensor Fault
12613       [E024] Relay Fault
12614       [E025] Internal Fan Fault
12615       [E026] External Fan Fault
12672       [E032] Bus Voltage Hard Fault
12674       [E012] BAT Voltage Fault
12675       [E013] BAK Voltage Fault
12676       [E028] DC BUS Voltage Low
12677       [E014] HW Fault
12678       [E015] Backup Load Fault
12679       [E016] Inverter Over Voltage
12680       [E011] Inverter Over Freq
12681       [E017] Inverter Over Current
12682       [E037] Phase Order Err
12736       [E019] SCI Fault
12737       [E018] FLASH Fault
12738       [E029] Meter Comm Fault
12739       [E031] AFCI Comm Fault
12768       [E400] BMS Comm Fault
12769       [E431] Abnormal Battery Voltage
12800       [E404] BAT Voltage Sensor Fault
12801       [E405] BAT Temperature Sensor Fault
12802       [E406] BAT Internal Comm Fault
12803       [E407] Input OV Fault
12804       [E408] Input Reversed Fault
12805       [E409] BAT Relay Checking Fault
12806       [E410] Cell Damaged Fault
12807       [E411] Shutdown Circuit Fault
12808       [E412] BMIC Fault
12809       [E413] BAT Internal Bus Fault
12810       [E414] Self-checking Fault
12811       [E415] Safety Function Fault
12812       [E416] ISO Fault
12832       [E417] Cell UV (Error)
12833       [E418] Cell OV (Error)
12834       [E419] Cluster UV (Error)
12835       [E420] Cluster OV (Error)
12836       [E421] Charge UT (Error)
12837       [E422] Charge OT (Error)
12838       [E423] Discharge UT (Error)
12839       [E424] Discharge OT (Error)
12840       [E425] Charge OC (Error)
12841       [E426] Discharge OC (Error)
12842       [E427] Battery Module UV (Error)
12843       [E428] Battery Module OV (Error)
12844       [E429] Terminal OT (Error)
12846       [E430] Abnormal Leakage (Error)
12864       [I400] Cell UV (Info)
12865       [I401] Cell OV (Info)
12866       [I402] Cluster UV (Info)
12867       [I403] Cluster OV (Info)
12868       [I404] Charge UT (Info)
12869       [I405] Charge OT (Info)
12870       [I406] Discharge UT (Info)
12871       [I407] Discharge OT (Info)
12872       [I408] Charge OC (Info)
12873       [I409] Discharge OC (Info)
12874       [I410] Battery Module UV (Info)
12875       [I411] Battery Module OV (Info)
12876       [I412] Terminal OT (Info)
12877       [I413] Abnormal Fan (Info)
12878       [I414] Abnormal Leakage (Info)
12896       [W400] Cell UV (Warning)
12897       [W401] Cell OV (Warning)
12898       [W402] Cluster UV (Warning)
12899       [W403] Cluster OV (Warning)
12900       [W404] Charge UT (Warning)
12901       [W405] Charge OT (Warning)
12902       [W406] Discharge UT (Warning)
12903       [W407] Discharge OT (Warning)
12904       [W408] Charge OC (Warning)
12905       [W409] Discharge OC (Warning)
12906       [W410] Battery Module UV (Warning)
12907       [W411] Battery Module OV (Warning)
12908       [W412] BMS Offline (Warning)
12910       [W414] SN Change of Module (Warning)
12911       [W415] Abnormal Change of Cluster Voltage (Warning)
12912       [W416] Abnormal Cluster △V (Warning)
12913       [W417] Abnormal Module △V (Warning)
13056       [S01] WorkMode Abnormal
13057       [S02] Emergency Stop
13058       [S03] DC Abnormal
13059       [S04] Mains Abnormal
13061       [S06] Off-Grid Battery Abnormal
13062       [S07] Enable Stop Command
13063       [S08] Soc Low and No PV
13066       [S11] Waiting for bypass state
13067       [S12] Standby state after firmware upgrading
13073       [S18] OverFreq PowerLimit
13074       [S19] OverTemp PowerLimit
13075       [S20] OverCurr PowerLimit
13076       [S21] Reactive PowerLimit
13077       [S22] Feed in Grid PowerLimit
13078       [S23] Slow Loading
13079       [S24] OverVolt PowerLimit
13080       [S25] System PowerLimit
13081       [S26] EMS command limit
1           [F101] Connection or network error
16864       Reduced grid charging capacity (§ 14a)
17569       [W104] Calibration charge
17570       [W103] Calibration charge not completed
18928       [F109] Mains energy meter not functioning
18931       [F110] Energy meter of the external PV system is not functioning
18933       [F111] External storage energy meter  not working
18938       [F112] User energy meter 1 is not functioning
18939       [F113] User energy meter 2 is not functioning
18940       [F114] User energy meter 3 is not functioning
18941       [F115] User energy meter 4 is not functioning
```

## batterX Business Series

```
ID          Description

5408        [A01] Output overcurrent
5409        [A02] Overtemperature shutdown
5410        [A03] Battery voltage high
5411        [A04] Output voltage low
5412        [A05] Output voltage high
5413        [A06] Overload shutdown
5414        [A07] Short circuit at output
5415        [A08] Maintenance bypass ON
5416        [A09] Load transfer to bypass
5417        [A10] Battery voltage too low
5418        [A11] EPO Shutdown
5419        [A12] DC-BUS balance bad
5420        [A13] High voltage at UPS output
5421        [A14] Inverter start fail
5422        [A15] POWER ON FAULT TRIP
5423        [A00] UPS AC-Output fault
5440        [A17] Bypass failure
5441        [A18] Bypass voltage out of range
5442        [A19] Bypass frequency out of range
5443        [A20] UPS output overload
5444        [A21] UPS output overtemperature
5445        [A22] UPS output OFF
5446        [A23] Automatic bypass ON
5447        [A24] Backfeed current to UPS output
5448        [A25] UPS AC-Output reset
5449        [A26] Battery low
5450        [A27] Generator mode
5451        [A28] UPS output phase loss
5452        [A29] Synchronisation problem at UPS output
5453        [A30] Short circuit at UPS output
5454        [A31] UPS Output switch OFF
5455        [A32] Service login
5456        [A33] UPS AC-Output test
5457        [A34] Bypass phase dislocation
5458        [A35] UPS output stop
5459        [A36] DC-BUS voltage too low
5460        [A37] UPS output current too high
5461        [A38] Fuse failure
5462        [A39] Inverter control board power supply failure
5463        [A40] UPS output starting
5464        [A41] UPS output in stand-by
5465        [A42] Parallel alarm
5466        [A43] User login
5467        [A44] WAITING MINIMUM
5468        [A45] Service password required
5469        [A46]
5470        [A47]
5471        [A48]
4384        [R01] AC input voltage too high
4385        [R02] AC input loss
4386        [R03] DC-BUS voltage too high
4387        [R04] DC-BUS voltage too low
4388        [R05] UPS input frequency out of range
4389        [R06] UPS input overtemperature
4390        [R07] AC input voltage loss
4391        [R08] Input overcurrent
4392        [R09] Input phase dislocation
4393        [R10] Fuse blown
4394        [R11]
4395        [R12]
4396        [R13]
4397        [R14] PFC manual stop
4398        [R15] Internal DC voltage too low
4399        [R00] UPS AC-Input fault
4416        [R17] Battery test
4417        [R18] Rectifier in boost charge mode
4418        [R19] AC input voltage too high
4419        [R20] Input breaker open
4420        [R21] PFC stop
4421        [R22] Positive battery charge current reached limit
4422        [R23] Negative battery charge current reached limit
4423        [R24] Waiting for higher DC-BUS voltage
4424        [R25] Battery test failed
4425        [R26] Battery temperature sensor fail
4426        [R27] Battery temperature too high
4427        [R28] Battery not connected
4428        [R29] UPS AC-Input reset
4429        [R30]
4430        [R31] UPS AC-Input starting
4431        [R32]
```